EasyManua.ls Logo

Panasonic CS-E7GKDW CU-E7GKD

Panasonic CS-E7GKDW CU-E7GKD
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
67
16.2. Sensible Capacity Chart
O CS-E7GKDW CU-E7GKD
O CS-E9GKDW CU-E9GKD
O CS-E12GKDW CU-E12GKD
220 - 230V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 2.03 1.54 0.44 1.90 1.48 0.47 1.77 1.42 0.51 1.61 1.35 0.55
19.0°C 2.05 0.48
19.5°C 2.23 1.61 0.45 2.09 1.55 0.48 1.94 1.49 0.52 1.77 1.42 0.56
22.0°C 2.43 1.67 0.46 2.27 1.61 0.49 2.12 1.55 0.52 1.92 1.48 0.57
220 - 230V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 2.58 1.96 0.54 2.41 1.88 0.58 2.24 1.80 0.62 2.04 1.71 0.67
19.0°C 2.60 0.59
19.5°C 2.83 2.05 0.55 2.65 1.97 0.59 2.46 1.89 0.63 2.24 1.80 0.68
22.0°C 3.09 2.12 0.56 2.88 2.04 0.60 2.68 1.97 0.64 2.44 1.88 0.70
220 - 230V Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 3.47 2.63 0.87 3.24 2.52 0.94 3.02 2.43 1.00 2.74 2.30 1.08
19.0°C 3.50 0.95
19.5°C 3.81 2.76 0.89 3.56 2.65 0.95 3.31 2.55 1.02 3.01 2.43 1.10
22.0°C 4.15 2.86 0.90 3.88 2.75 0.97 3.61 2.65 1.04 3.28 2.53 1.12
TC
SHC
IP
-
-
-
Total Cooling Capacity (kW)
Sensible Heat Capacity (kW)
Input Power (kW)
Indoor 27°C/19°C
Outdoor 35°C/24°C