114
TC: Cooling Capacity IPT: Cooling Power Consumption
Model Cooling capacities are based on conditions
CS-F50DTE5 3 phase, 50Hz 400V
Cooling capacity Indoor temp. 27°C D.B. 19°C W.B.
13.5kW Outdoor temp. 35°C D.B.
Standard air volume 32 m
3
/min
Ambient Temperature Air Entering Condenser (°C D.B.)
Return 25°C30°C35°C40°C43°C
Air TCTCTCTCTC
D.B. W.B. kW kW kW kW kW
17 14.05 13.50 12.70 11.75 11.06
23 19 14.84 14.38 13.64 12.72 12.07
22 16.21 15.77 15.05 14.08 13.41
17 13.89 13.35 12.58 11.66 11.00
25 19 14.86 14.34 13.57 12.64 11.98
22 16.20 15.71 14.94 13.91 13.29
17 13.72 13.19 12.45 11.58 10.95
27 19 14.88 14.31 13.50 12.56 11.88
22 16.19 15.64 14.82 13.77 13.16
17 13.69 13.20 12.42 11.67 11.09
29 19 14.85 14.31 13.51 12.65 12.03
22 16.12 15.57 14.73 13.79 13.15
17 13.67 13.20 11.55 11.73 11.18
32 19 14.82 14.31 13.51 12.72 12.12
22 16.08 15.53 14.71 13.80 13.15
Ambient Temperature Air Entering Condenser (°C D.B.)
Return 25°C30°C35°C40°C43°C
Air IPT IPT IPT IPT IPT
D.B. W.B. kW kW kW kW kW
17 4.20 4.55 4.96 5.44 5.77
23 19 4.46 4.82 5.26 5.76 6.11
22 4.81 5.21 5.68 6.23 6.60
17 4.21 4.55 4.95 5.40 5.73
25 19 4.48 4.84 5.27 5.75 6.10
22 4.84 5.23 5.69 6.21 6.58
17 4.21 4.54 4.94 5.37 5.69
27 19 4.50 4.85 5.28 5.74 6.08
22 4.86 5.24 5.70 6.20 6.57
17 4.19 4.53 4.88 5.24 5.46
29 19 4.48 4.84 5.22 5.60 5.84
22 4.93 5.33 5.75 6.17 6.43
17 4.17 4.52 4.84 5.16 5.31
32 19 4.46 4.83 5.18 5.51 5.68
22 4.97 5.40 5.78 6.15 6.49