Time Graph for Overload Deicing
abcdefghi j k
l
m
nopq
49
Max
12’
<Operation status>
Overload controla-i
i-l Overload deicing(timer)
l-m: Warm booting control
m-r Overload control
Out door fan stop for 60' accumulatively
20’’ 20’’
51
Outdoor Heat
Exchanger
Outdoor Heat
Exchanger
10’’ 20’’
Basic time
Compressor
Indoor fan
Outdoor fan
Operation Indicator
4-way valve
)g-h (Indoor fan stop)
h-i (Indoor fan”SL.”)
Operation
Stop
Blink
Time
27
CS-PA7DKD / CU-PA7DKD / CS-PC7DKD / CU-PC7DKD