D. IPM Protection Control
1. DC Peak Current Control
When electric current to IPM exceeds set value of DC17.3 ± 1A, the compressor will stop. It will restart after three
minutes.
If the set value is exceeded again within 30 seconds, the operation will restart after one minute.
Error code [F99] will be displayed.
2. Overheating Protection Control
When the IPM temperature rises to 90°C, compressor will stop immediately.
Compressor restarts after three minutes if the temperature decreases to 85°C.