81
nanoe-G check mode
o To enable nanoe-G check mode, during nanoe-G operation ON:
SET
SET
Transmit ECO demo code
and after 2 seconds return to normal
mode.
Press continously for 15s
SET
Transmit check code
and after 2 seconds return to normal
mode.
SET
Transmit sunlight sensor check code
and after 2 seconds return to normal
mode.
Remote control normal mode
o If there is abnormal discharge, nanoe-G indicator blinks immediately.
Error detection control
When nanoe-G indicator blinks, it indicates error listed below:
o Nanoe-G connector at main PCB open
Judgment method
During nanoe-G operation, nanoe-G connector at main PCB is opened.
Troubleshooting method
Connect the connector or stop operation to cancel the blinking.
Switch off the power supply and unplug before cleaning.
Clean the dirty nanoe-G generator with cotton bud.
o Abnormal discharge error
Judgment method
During nanoe-G operation, the nanoe-G system has abnormal discharge due to short-circuit caused
by water or dust adhesion and so forth, with Lo-feedback voltage (at microcontroller).
When abnormal discharge occurred, every 30 minutes the unit supplies power to the nanoe-G
system.
When abnormal discharge occurs for 48 times continuously, nanoe-G indicator blinks.
Troubleshooting method
Press nanoe-G button or OFF/ON button to stop the operation and check the nanoe-G connector at
PCB.
After that, press nanoe-G button again to confirm the nanoe-G indicator do not blinks.
The 24 timer counter will be clear after 10 minutes of normal operation or when operation stops.
Error reset method
Press “OFF/ON” button to OFF the operation.
Press AUTO OFF/ON button at indoor unit to OFF the operation.
OFF Timer activates.
Power supply reset.