9 OPERATION RANGE
The applicable voltage range for each unit is given in “the following table”. The working voltage among the three phases
must be balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher
than 85% of the rated voltage.
Power Supply
Model
CU-
Unit Main Power Applicable Voltage
Phase, Volts Hz Maximum Minimum
W50BBP8 V50BBP8 3N~380 50 418 342
3N~400 50 440 360
3N~415 50 457 374
Indoor and Outdoor Temperature
Q
QQ
Q
Cooling only type
Model 50Hz ... V50BBP8
Operating Hz Indoor Temp. (D.B./W.B.) (°C) Outdoor Temp. (D.B./W.B.) (°C)
Maximum Minimum Maximum Minimum
Cooling 50 32/23 21/15 43/- -5/-
Q
QQ
Q
Heat pump type
Model 50Hz ... W50BBP8
Operating Hz Indoor Temp. (D.B./W.B.) (°C) Outdoor Temp. (D.B./W.B.) (°C)
Maximum Minimum Maximum Minimum
Cooling 50 32/23 21/15 43/- -5/-
Heating 50 27/- 16/- 24/18 -10/-