4. Service Data 
Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced 
heating mode. 
4.1  Cool Mode Outdoor Air Temperature Characteristic 
Condition 
  Indoor room temperature: 26.7°C (80°F) Dry Bulb/19.4°C (67°F) Wet Bulb 
  Unit setting: Standard piping length, forced cooling at 16°C (60.8°F), Hi fan 
  Compressor frequency: Rated for cooling operation 
  Piping Length: 7.5 m (24.6 ft) 
 Voltage: 208V/230V 
4.1.1 CS-XE12SKUA-1  CU-XE12SKUA-1 
 
 
 
 
 
 
 
 
 
Current
(A)
Gas Side Piping
Pressure(PSI (MPa))
Indoor Discharge
Air Temprature
(°F (°C))
208
230
60.0 (15.5)
61.0 (16.1)
62.0 (16.6)
63.0 (17.2)
64.0 (17.7)
65.0 (18.3)
66.0 (18.8)
67.0 (19.4)
2.500
3.000
3.500
4.000
4.500
5.000
120.000 (0.827)
125.000 (0.861)
130.000 (0.896)
135.000 (0.930)
140.000 (0.965)
145.000 (0.999)
150.000 (1.034)
155.000 (1.068)
160.000 (1.103)
165.000 (1.137)
-4
(-20.0)
6
(-14.4)
16
(-8.8)
26
(-3.3)
36
(2.2)
46
(7.7)
56
(13.3)
66
(18.8)
76
(24.4)
86
(30.0)
96
(35.5)
106
(41.1)
116
(46.6
Outdoor Air Temperature (°F (°C))
-4
(-20.0)
6
(-14.4)
16
(-8.8)
26
(-3.3)
36
(2.2)
46
(7.7)
56
(13.3)
66
(18.8)
76
(24.4)
86
(30.0)
96
(35.5)
106
(41.1)
116
(46.6)
Outdoor Air Temperature (°F (°C))
-4
(-20.0)
6
(-14.4)
16
(-8.8)
26
(-3.3)
36
(2.2)
46
(7.7)
56
(13.3)
66
(18.8)
76
(24.4)
86
(30.0)
96
(35.5)
106
(41.1)
116
(46.6)
Outdoor Air Temperature (°F (°C))