10.2.5 Connect The Cable To The Outdoor Unit
1. Remove the control board cover metal from
the unit by loosening two screws.
2. Cable connection to the power supply through
isolating Devices (Disconnecting means).
o Connect approved type polychloroprene
sheathed power supply cord 3 x
2.5 mm
2
245 IEC 57 type designation or
heavier cord to the terminal board, and
connect the others end of the cord to
Isolating Devices (Disconnecting means).
3. Connecting cable between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 x 1.5 mm
2
flexible
cord, type designation 245 IEC 57 or heavier
cord.
4. Connect the power supply cord and
connecting cable between indoor unit and
outdoor unit according to the diagram as
shown.
5. For wire stripping and connection requirement, refer to the diagram below.
6. Secure the power supply cord and connecting cables onto the control board with the holder.
7. Attach the control board cover back to the original position with screw.
This equipment must be properly earthed.
Note: Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.