50
Control Contents
Compressor frequency and outdoor fan speed maximum limit is set. Adjust accordingly.
Compressor frequency Outdoor fan speed
Cool/Quiet #30 Hz #400 rpm
Cancel Condition
o Indoor fan speed is equal or higher than Lo fan.
o > 1 operation indoor unit.
o In any cooling overload zone.
o During annual cooling
o Initial frequency operation.
o During starting control.
o During “Electronic part temperature rise protection by outdoor air & total current”
o During “Electronic part temperature rise protection by total current”
o During “IPM temperature rise prevention control”
o Not during cool mode
When any above is satisfied.