13
English
7. The following leak detection  
    methods are deemed 
    acceptable for all refrigerant 
    systems
• 
No leaks shall be detected when 
using detection equipment with 
a sensitivity of 5 grams per year 
of refrigerant or better under a 
pressure of at least 0.25 times the 
maximum allowable pressure 
(>1.04 MPa, max 4.15 MPa), for 
example, a universal sniffer.
• 
Electronic leak detectors may 
be used to detect fl ammable 
refrigerants, but the sensitivity may 
not be adequate, or may need re-
calibration.
(Detection equipment shall be 
calibrated in a refrigerant-free area.)
• 
Ensure that the detector is not a 
potential source of ignition and is 
suitable for the refrigerant used.
• 
Leak detection equipment shall be 
set at a percentage of the LFL of the 
refrigerant and shall be calibrated 
to the refrigerant employed and the 
appropriate percentage of gas (25 % 
maximum) is confi rmed.
• 
Leak detection fl uids are also 
suitable for use with most 
refrigerants, for example, bubble 
method and fl uorescent method 
agents. The use of detergents 
containing chlorine shall be avoided 
as the chlorine may react with the 
refrigerant and corrode the copper 
pipe-work.
• 
If a leak is suspected, all naked 
fl ames shall be removed/
extinguished.
• 
If a leakage of refrigerant is found 
which requires brazing, all of the 
refrigerant shall be recovered from 
the system, or isolated (by means 
of shut off valves) in a part of the 
system remote from the leak. The 
precautions in #8 must be followed 
to remove the refrigerant.
 
8. Removal and evacuation
• 
When breaking into the refrigerant 
circuit to make repairs – or for 
any other purpose – conventional 
procedures shall be used. However, 
it is important that best practice 
is followed since fl ammability is 
a consideration. The following 
procedure shall be adhered to: 
remove refrigerant -> purge the 
circuit with inert gas -> evacuate 
-> purge with inert gas -> open the 
circuit by cutting or brazing.
• 
The refrigerant charge shall be 
recovered into the correct recovery 
cylinders.
• 
The system shall be purged with 
OFN to render the appliance safe.
• 
This process may need to be 
repeated several times.
• 
Compressed air or oxygen shall not 
be used for this task.
• 
Purging shall be achieved by 
breaking the vacuum in the system 
with OFN and continuing to fi ll until 
the working pressure is achieved, 
then venting to atmosphere, and 
fi nally pulling down to a vacuum.
• 
This process shall be repeated until 
no refrigerant is within the system.
• 
When the fi nal OFN charge is used, 
the system shall be vented down 
to atmospheric pressure to enable 
work to take place.
• 
This operation is absolutely vital if 
brazing operations on the pipe work 
are to take place.
• 
Ensure that the outlet for the 
vacuum pump is not close to any 
potential ignition sources and there 
is ventilation available.
OFN =  oxygen free nitrogen, 
type of inert gas.
 
Safety Precautions