• Compressor high pressure protection
 − If the indoor heat exchanger becomes 68°C or more, the compressor will stop and restart automatically.
 − Time Delay Safety Control is activated before the compressor restart.
8.5.9. 4-Way Valve Control
 • 4-way valve always on during Heating operation. (except deicing operation)
 • When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
 • This is to prevent the refrigerant flow process sound for being occur.
8.5.10. Outdoor Fan Motor Control
 • When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation).
 • This is to release the heat and to obtain the lowest pressure as fast as possible.
8.5.11. Hot Start Control
 • Hot Start Control is to prevent cool air discharge into the room when heating operation start.
 • When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
 • Hot start is completed when indoor heat exchanger rises to 42°C or operation over 4 minutes.