12 Operation Control (CU-3E18LBE and CU-4E23LBE)
12.1. Cooling Operation
12.1.1. Outdoor fan control
When cooling operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure
below:
12.1.2. Annual Cooling control
This control is to enable cooling operation when outdoor ambient temperature is low.
Control start conditions:
- Cooling operation is activated with compressor ON.
- Outdoor ambient temperature is less than 15°C
Control contents:
- When the above conditions are fulfilled, based on outdoor pipe temperature, the outdoor fan motor will operate according to
figure below:
To improve the judgment accuracy during annual cooling control, outdoor ambient temperature sampling for 2 minutes will be
activated every 35 minutes under designated fan speed.
Control stop conditions:
- When either one of the start conditions are not complied.