14.5. Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
- For 5 minutes, the compressor continuously operates and outdoor total current is between 1.5A and 1.88A.
- During Cooling and Soft Dry operations:
- Indoor heat exchanger temperature is above 20°C.
- During heating operations:
- Indoor heat exchanger temperature is below 25°C.
Control contents
- Compressor stops (and restart after 3 minutes).
- If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated (Refrigeration cycle abnormality).
14.6. 4-Way Valve Failure Protection Control
During Cooling operation
- 4 minutes after compressor started, if the temperature of the indoor unit heat exchanger exceeds 45°C, the compressor stops
(After 3 minutes, Time delay safety control starts).
- If this situation occurs 4 times within 30 minutes, TIMER LED blinks (F11 error)
During Heating operation
- 4 minutes after compressor started, if the temperature of the indoor unit heat exchanger drops below 5°C, the compressor
stops (After 3 minutes, Time delay safety control starts).
- If this situation occurs 4 times within 30 minutes, TIMER LED blinks (F11 error)
14.7. Protection Control for Cooling & Soft Dry Operation
14.7.1. Cooling overload control
Detects the outdoor pipe temperature and carry below restriction/ limitation (limit the compressor operation frequency).
If the outdoor heat exchanger temperature exceeds 52°C during cooling / dry operation, the compressor frequency is restricted.
If the compressor if outdoor pipe temperature exceeds 62°C.
If the compressor stops 4 times within 20 minutes, TIMER LED blinks (F95: outdoor high pressure rise protection)