75
12.2.4 Connect the Cable to the Indoor Unit
1 The inside and outside connecting cable can
be connected without removing the front grille.
2 Connection cable between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 x 1.5 mm
2
flexible
cord, type designation 245 IEC 57 or heavier
cord.
3 Bind all the indoor and outdoor connecting
cable with tape and route the connecting
cable via the escapement.
4 Remove the tapes and connect the
connecting cable between indoor unit and
outdoor unit according to the diagram below.
5 Secure the connecting cable onto the control board with the holder (clamper).
o Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s
respectively.
o Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.