9.11. Pump Down Operation
When pushing the [PUMP DOWN] button on the outdoor PCB for 1 second, pump down operation start. Detail of pump down
operation is shown at below table.
During pump down operation, push the [PUMP DOWN] button once again for 1 second, pump down operation stop.
After 600[Sec] past, pump down operation stop.
9.12. Indoor Air Volume Up Control (DC Fan Motor Type Only)
Indoor air volume up control set by local setting mode of wired or wireless remote controller.
(item 01, 00: standard / 01: Air volume up mode)
(only for DC motor type)
Due to air volume up control, indoor fan revolution increase in case of Hi speed setting only.
This control is memorized in the micro computer, it cannot be reset by power off.
33
CS-F34DB4E5 CU-L34DBE5 / CS-F43DB4E5 CU-L43DBE5