15 CAPACITY AND POWER CONSUMPTION
15.1. HEATING PERFORMANCE
Model Heating capacities are based on conditions below.
CS-W50BTP
O 3 phase, 50Hz, 400V
O Indoor temperature 20°C D.B.T.
O Outdoor temperature 7°C D.B. 6°C W.B.T.
O Standard air volume 35m
3
/min
CU-W50BBP8
Heating capacity 14.0 kW
Inlet Air Outdoor Temperature (°C W.B.T.)
Air Volume (m
3
/min) Entering Air
D.B.T. (°C)
-6°C 0°C 6°C 12°C
H.C. IPT H.C. IPT H.C. IPT H.C. IPT
15 11.68 3.82 14.00 4.36 16.8 5.18 19.5 6.10
35 20 11.04 4.03 13.20 4.63 16.0 5.45 19.2 6.32
25 10.40 4.25 12.48 4.91 15.2 5.72 18.4 6.52
H.C. = Heating Capacity
IPT = Power Consumption