8-8-5. Indicating (marking) the indoor and outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that the
indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and
use a magic marker or similar means which cannot be easily erased to indicate the numbers in an easily visible
location on the indoor units (near the indoor unit nameplates).
Example: (Outdoor) 1 - (Indoor) 1-1...(Outdoor) 2 - (Indoor) 2-2...
(2) These numbers will be needed for maintenance. Be sure to indicate them.
* Use the remote controller to check the addresses of the indoor units. Press and hold the button and
button for 4 seconds or longer (simple settings mode). Then press the button and select the indoor
address. (Each time the button is pressed, the address changes as follows: 1-1, 2-1, ....) The indoor unit fan
operates only at the selected indoor unit. Confi rm that correct fan is operating, and indicate address on the
indoor unit.
Press the button again to return to the normal remote control mode.
For details, refer to the separate handbook.
8-8-6. Main-sub remote controller control
Control using 2 remote controller switches
Main-sub remote controller control refers to the use of 2 remote controllers to control 1 indoor unit.
(A maximum of 2 remote controllers can be connected.)
Connecting 2 remote controllers to
control 1 indoor unit
1 2
1 2
1 2
U1U2
U1U2
Remote control wiring
Optional
Optional
Remote controller
switch (sub)
Remote controller
switch (main)
Indoor unit
Outdoor unit
Ground
Ground
for remote
control wiring
Terminal plate
RCU. Main/Sub
MainSub
CODE
DATA
ITEM
Clock display
12 hours
(AM/PM)
24 hours
RCU. CK
NormalRCU. CK
Room temperature sensor
Main unit RCU
Remote controller setting mode
To set the remote controller main/sub setting or change the sensor, follow the steps below.
Press both
and buttons on the remote controller for more than
4 seconds together.
Select CODE No. with buttons.
Change DATA with
/
(TIMER) buttons.
Press
. Finally, press
.
*
*
Make sure to set [Normal] for RCU. CK.
DATA is memorized in the RCU. (DATA setting will not
be changed even when the power is turned off.)