16
Insulation material 
The material used for insulation must have good insulation 
characteristics, be easy to use, be age resistant, and must not 
easily absorb moisture.
Never grasp the drain or refrigerant connecting outlets 
when moving the unit. 
CAUTION
After a tube has been insulated, never try to bend it into a 
narrow curve because it can cause the tube to break or crack.
5-4. Taping the Tubes
(1)  At this time, the refrigerant tubes (and electrical wiring if 
local codes permit) should be taped together with armoring 
tape in 1 bundle. To prevent the condensation from 
overflowing the drain pan, keep the drain hose separate 
from the refrigerant tubing.
(2)  Wrap the armoring tape from the bottom of the outdoor 
unit to the top of the tubing where it enters the wall. As you 
wrap the tubing, overlap half of each previous tape turn.
(3)  Clamp the tubing bundle to the wall, using 1 clamp approx. 
each meter. (Fig. 5-8)
Fig. 5-8
N OT E
Donotwindthearmoringtapetootightlysincethiswill
decrease the heat insulation effect. Also ensure that the 
condensation drain hose splits away from the bundle and drips 
clear of the unit and the tubing.
5-5. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing 
putty to seal off the hole in the wall to prevent rain and draft 
from entering. (Fig. 5-9)
Fig. 5-9
6. 
HOW TO INSTALL TIMER REMOTE 
CONTROLLER OR HIGH-SPEC WIRED 
REMOTE CONTROLLER (OPTIONAL PART)
N OT E
Refer to the Operating Instructions attached to the optional Timer 
Remote Controller or optional High-spec Wired Remote Controller.
●  For the flare nuts at tubing connections, be sure to use the 
flare nuts that were supplied with the unit, or else flare nuts 
for R410A (type 2). The refrigerant tubing that is used must 
be of the correct wall thickness as shown in the table.
Tube diameter
Tightening torque, 
approximate
Tube thickness
ø6.35(1/4")
14 – 18 N · m 
{140 – 180 kgf · cm}
0.8 mm
ø9.52(3/8")
34 – 42 N · m 
{340 – 420  kgf · cm}
0.8 mm
ø12.7(1/2")
49 – 61 N · m 
{490 – 610  kgf · cm}
0.8 mm
ø15.88(5/8")
68 – 82 N · m 
{680 – 820  kgf · cm}
1.0 mm
ø19.05(3/4")
100 – 120 N · m 
{1000 – 1200  kgf · cm}
1.0 mm
  Because the pressure is approximately 1.6 times higher than 
conventional refrigerant pressure, the use of ordinary flare 
nuts (type 1) or thin-walled tubes may result in tube rupture, 
injury, or asphyxiation caused by refrigerant leakage.
●  In order to prevent damage to the flare caused by over-
tightening of the flare nuts, use the table above as a guide 
when tightening.
●  When tightening the flare nut on the liquid tube, use an 
adjustable wrench with a nominal handle length of 200 mm.
5-3. Insulating the Refrigerant Tubing
Tubing Insulation
●  Thermal insulation must be applied to all unit tubing, 
including distribution joint (purchased separately). 
Fig. 5-7
*  For gas tubing, the insulation material must be heat 
resistant to 120°C or above. For other tubing, it must be 
heat resistant to 80°C or above.
  Insulation material thickness must be 10 mm or greater.
  IftheconditionsinsidetheceilingexceedDB30°CandRH
70%, increase the thickness of the gas tubing insulation 
material by 1 step.
CAUTION
If the exterior of the outdoor unit valves has been finished 
with square duct covering, make sure you allow sufficient 
space to use the valves and to allow the panels to be 
attached and removed.
N OT E
Gas Leakage Detector
Note that the gas leakage detector should be capable of 
detecting the refrigerant R410A.
Air Purging
Refer to “AIR PURGING” in the separate Installation 
Instructions for the outdoor unit in regard to air purging with a 
vacuum pump (for test run) preparation.
Taping the flare nuts
Cover up the tubing connections with the supplied flare 
insulator. Then fasten the insulator at both ends with the vinyl 
clamps (field supply).
Insulated tubes
Drainhose
Clamp
Liquid tubing
Gas tubing
Insulation
Two tubes arranged together
Apply putty here
Tubing
Pana_F616380_All_L.indb   16 2013-12-11   17:38:12