2-2. Shield for Horizontal Exhaust Discharge
It is necessary to install an air-discharge chamber (eld supply) 
to direct exhaust from the fan horizontally if it is difcult to 
provide a minimum space of 2 m between the air-discharge 
outlet and a nearby obstacle. 
CAUTION
In regions with heavy snowfall, the 
outdoor unit should be provided with a 
solid, raised platform and snow-proof 
vents. 
AVOID
DO
Without snow-proof vents 
(Without platform)
With snow-proof vents 
(High platform)
Fallen 
snow
2-3. Installing the Outdoor Unit in Heavy Snow Areas
In locations where wind-blown snow can be a problem, snow-
proof vents should be tted to the unit and direct exposure to 
the wind should be avoided as much as possible.  
The following problems may occur if proper countermeasures 
are not taken:
●  The fan in the outdoor unit may stop running, causing the 
unit to be damaged.
●  There may be no air flow.
●  The tubing may freeze and burst.
●  The condenser pressure may drop because of strong wind, 
and the indoor unit may freeze.
2-4. Precautions When Installing in Heavy Snow 
Areas
a)  The platform should be higher than the maximum snow 
depth.
b)  The 2 anchoring feet of the outdoor unit should be used for 
the platform, and the platform should be installed beneath 
the air-intake side of the outdoor unit.
c)  The platform foundation must be solid and the unit must be 
secured with anchor bolts.
d)  When installing on a roof subject to strong wind, 
countermeasures must be taken to prevent the unit from 
being overturned.
2-5.  Dimensions of Wind Ducting 
Reference diagram for air-discharge chamber 
(field supply)
  For further details, see section “SUPPLEMENT”.
2-6. Dimensions of Snow Ducting 
Reference diagram for snow-proof vents  
(field supply)
  For further details, see section “SUPPLEMENT”.