2. Installation location of R32 refrigerant leakage detection sensor
When installing R32 refrigerant leakage detection sensor away from the indoor unit, place it
at 300 mm or less from a floor surface and satisfy the condition either (1) or (2) below.
(1) If no obstacles exist in a straight line from R32 refrigerant leakage detection sensor to the
indoor unit, wall distance should be within 10 m in horizontal straight line.
A
B
Indoor unit
Indoor unit
Indoor unit
A : Top View
B : Front View
10 m or less
10 m or less
R32 refrigerant leakage
detection sensor
R32 refrigerant leakage
detection sensor
R32 refrigerant leakage
detection sensor
300 mm or less
(2) If obstacles exist in a straight line from R32 refrigerant leakage detection sensor to the
indoor unit, wall distance should be within 7 m in horizontal straight line.
A
B
Indoor unit
Obstacles
Obstacles
Obstacles
7 m or less
7 m or less
Indoor unit
Indoor unit
A : Top View
B : Front View
R32 refrigerant leakage
detection sensor
R32 refrigerant leakage
detection sensor
R32 refrigerant leakage
detection sensor
300 mm or less