4 - 11
2WAY SYSTEM 
Outdoor Unit Maintenance Remote Controller
4
5. Outdoor Unit Alarm History Monitor
•  
Displays outdoor unit alarms only.
•  
Check the indoor unit alarm histories separately using the 
indoor unit remote controllers or other control device.
<Operating procedure>
À
  Press and hold the   (CHECK) button and   
button simultaneously for 4 seconds or longer to engage 
outdoor unit alarm history mode.
  During temperature monitoring, 
 illuminates.
  The display and operations are the same as for the 
alarm history monitor performed from the indoor unit 
remote controller. However the “unit No.” display shows 
the outdoor unit address.
Á
 
Press the    button and select the outdoor unit for 
which to monitor the alarm history.
Â
  Press the temperature setting   and   
buttons and select the item code for the alarm history.
  The select outdoor unit address, the item code, and the 
alarm history (alarm data) are displayed.
  The outdoor unit address is displayed as R.C. XX-YY. 
System XX = Outdoor unit system address 
R.C. XX = Outdoor unit system address 
   YY = Outdoor unit sub-bus address 
  Item codes 01-08 are displayed. 01 indicates the most 
recent alarm.
  The alarm history displays the alarm code. (If no alarm 
are present, then -- -- is displayed.)
Ã
  To clear the alarm history, press the   button. (The 
outdoor unit alarm history will be cleared.)
Ä
  To exit, press the   (CHECK) button. The display 
returns to the normal display.
Display of unit No. 1 (main unit)
RemarksDescriptionDN
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
Indoor unit intake temp. (TA)
Indoor unit heat exchanger temp. E1 (E1)
—
Indoor unit heat exchanger temp. E3 (E3) Indoor unit
Discharge air temp. (BL)
Discharge air temp. setting
Indoor unit MOV pulse (MOV) STEP
Discharge temp. 1 (DISCH1)
Discharge temp. 2 (DISCH2)
High-pressure sensor temp.
Heat exchanger gas 1 (EXG1)
Heat exchanger liquid 1 (EXL1)
Heat exchanger gas 2 (EXG2)
Heat exchanger liquid 2 (EXL2)
Outdoor air temp. (TO)
—
AInverter primary current 1
A
A
CT2 Outdoor unit
STEPMOV pulse 1 (MOV1)
STEPMOV pulse 2 (MOV2)
Discharge temp. 3 (DISCH3) 
CT3
Actual operating frequency
STEPMOV pulse 4 (MOV4)
—
—
Low-pressure sensor temp.
Suction temp. (SCT)
Detected oil temp. 1 (OIL1)
Detected oil temp. 2 (OIL2)
Detected oil temp. 3 (OIL3)
—
Temp. sensor at refrigerant gas outlet of dual-tube temp. (SCG)
Hz
NOTE
0A and subsequent items are outdoor unit data. 0A – 24 are for unit No. 1.
2A – 44 are for unit No. 2. 4A – 64 are for unit No. 3.
SM830228-013WAYECO-iSYSTEM.in1010 2013/07/
1
4 2
5
3
SM830204-05_2WAY SYS.indb   11 2015/01/23   11:57:00