2WAY SYSTEM 
Remote Controller Functions
5 - 7
1. Simple Settings Function
5
When the operating mode at the priority remote controller is changed, the operating modes of other remote 
controllers change as shown below.
Mode change at priority  remote controller Operating modes at other remote controllers
Current mode  New mode  Current mode New mode
Cooling or dry Heating
Cooling or dry Heating 
Fan Fan (not changed)
Heating Cooling
Heating Cooling
Fan Fan (not changed)
Cooling Dry
Cooling Cooling (not changed)
Dry Dry (not changed)
Heating Dry
Heating Cooling
Fan Fan (not changed)
Cooling or dry Fan
Cooling Cooling (not changed)
Dry Dry (not changed)
Fan Fan (not changed)
Heating Fan
Heating Heating (not changed)
Fan Fan (not changed)
Item code Item Description
05
Fan speed setting when 
heating thermostat is OFF
Changes the fan speed setting when the heating thermostat is OFF.
06
Heating intake temperature 
shift
Shifts the intake temperature during heating. 
Can be set when the body thermostat is used.
07 Electric heater installation
Set when cost distribution is performed using an AMY central control system 
or similar system, and when an optional electric heater is installed. 
(This is unrelated to control of the electric heater.)
08
Humidifying when heater 
thermostat is OFF
Normally humidifying does not occur when the thermostat is OFF during 
heating operation. However, this setting can be changed in order to increase 
the amount of humidifying.
Caution: In order to avoid water leakage and damage to the fan, do not use 
this setting unless a vaporizing humidifier is used.
0D
Permit/prohibit automatic 
heating/cooling
This setting can be used to prevent the automatic heating/cooling display on 
the remote control if the unit configuration permits automatic heating/cooling 
operation.
0F Cooling-only
This setting allows a heat pump indoor unit to be operated as a cooling-only 
unit.
SM830204-05_2WAY SYS.indb   7 2015/01/23   11:57:26