2WAY SYSTEM 
Control Functions
-
Outdoor Unit
1 - 10
1
3-7-4. Primary current protection of HIC board
The fan motor current is included in primary current. PCB is protected from the power consumption increase of 
fan motor when the heat exchanger is blocked by frost, etc.
Limit current 1
Max. current 1L
Stop
If this current is detected at regular intervals, alarm appears. 
Frequency of inverter compressor goes down.
Frequency of inverter compressor can increase.
Frequency of inverter compressor cannot increase.
Max. current 1H
Reference
Inverter layout
Diode Bridge 
Power Source 
IPM(FN) 
Magnet SW 
Noise Filter 
L3 
L1 
L2 
Noise Filter IPM(CM) 
Fan Motor 
Compressor 
W 
U 
V 
W 
U 
V 
Primary CT
Secondary CT
*When restarting after stopping by protection control, the compressor capacity will increase slowly.
2WAY SYSTEM
Control Functions-Outdoor Unit
3. Compressor Control
Limit current 1
Primary 
current
Max. current 1 H
unit : Amp.
10HP
19.8
16.8
15.8
8HP
15.1
12.1
11.1
12HP
18.0
15.0
14.0
14HP
21.0
18.0
17.0
16HP
21.0
18.0
17.0
18HP
21.0
18.0
17.0
20HP
21.0
18.0
17.0Max. current 1 L