IMPORTANT!
Please Read Before Starting
This air conditioner must be installed by the sales dealer 
or installer.
This information is provided for use only by authorized 
persons.
For safe installation and trouble-free operation, you 
must:
●
  Carefully read this instruction booklet before beginning.
●
  Follow each installation or repair step exactly as shown.
●
  This air conditioner shall be installed in accordance with 
National Wiring Regulations.
●
  This product is intended for professional use. 
Permission from the power supplier is required when  
installing the U-8MF3R7 outdoor unit that is connected 
to a 16 A distribution network.
●
  This equipment complies with EN/IEC 61000-3-12 
provided that the short-circuit power Ssc is greater than 
or equals to the values corresponding to each model as 
shown in the table below at the interface point between 
the user’s supply and the public system. 
It is the responsibility of the installer or user of the 
equipment to ensure; by consultation with the distribution 
network operator if necessary that the equipment is 
connected only to supply with a short-circuit power Ssc 
greater than or equals to the values corresponding to 
each model as shown in the table below.
U-10MF3R7 U-12MF3R7
Ssc 1,600 kVA 1,600 kVA
U-14MF3R7 U-16MF3R7
Ssc
2,000 kVA 2,150 kVA
●
  The product meets the technical requirements of  
EN/IEC 61000-3-3.
●
  Pay close attention to all warning and caution notices 
given in this manual.
 
WARNING
This symbol refers to a hazard or unsafe 
practice which can result in severe 
personal injury or death.
 
CAUTION
This symbol refers to a hazard or unsafe 
practice which can result in personal 
injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation 
sites and maintenance conditions. If you require help for a 
special problem, contact our sales/service outlet or your 
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for 
improper installation or maintenance service, including 
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
 
WARNING  When Wiring
WARNING
Risk of Electric Shock
ELECTRICAL SHOCK CAN 
CAUSE SEVERE PERSONAL 
INJURY OR DEATH. ONLY A 
QUALIFIED, EXPERIENCED 
ELECTRICIAN SHOULD 
ATTEMPT TO WIRE THIS  
SYSTEM.
• Do not supply power to the unit until 
all wiring and tubing are completed or 
reconnected and checked.
• Highly dangerous electrical voltages are 
used in this system. Carefully refer to the 
wiring diagram and these instructions 
when wiring. Improper connections 
and inadequate grounding can cause 
accidental injury or death.
• Connect all wiring tightly. Loose wiring 
may cause overheating at connection 
points and a possible fire hazard.
• Provide a power outlet to be used 
exclusively for each unit.
• ELCB must be incorporated in the 
fixed wiring. Circuit breaker must be 
incorporated in the fixed wiring in 
accordance with the wiring regulations.
Circuit 
breaker
U-14MF3R7
40 A
U-16MF3R7
40 A
Circuit 
breaker
U-8MF3R7
25 A
U-10MF3R7
25 A
U-12MF3R7
30 A
• Provide a power outlet exclusively for 
each unit, and full disconnection means 
having a contact separation by 3 mm 
in all poles must be incorporated in the 
fixed wiring in accordance with the wiring 
rules.
•  To prevent possible hazards from 
insulation failure, the unit must be 
grounded.
•  This equipment is strongly recommended 
to be installed with Earth Leakage 
Circuit Breaker (ELCB) or Residual 
Current Device (RCD). Otherwise, it may 
cause electrical shock and fire in case 
of equipment breakdown or insulation 
breakdown.