34
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction. 
A fire hazard may also exist. 
Therefore, ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the instructions on “How to Connect Wiring to Terminal” and fasten the wire 
securely with the fixing screw of the terminal board.
4-4. Connecting Multiple Indoor Units to a Single Solenoid Valve Kit
●  It is possible to connect plural indoor units to one solenoid valve kit. The indoor units can be controlled individually or be operated as 
a group.
●  It is possible to adopt plural indoor units with a common use of the solenoid valve kit per piece of refrigerant.
●  Categories of connected indoor unit capacities are determined by the solenoid valve kit.
Type of solenoid valve kit Total capacity of indoor units (kW)
CZ-P160HR3 5.6 < Total capacity ≤ 16.0
CZ-P56HR3 Total capacity ≤ 5.6
* If the capacity range is exceeded, use two solenoid valves connected in parallel.
Each Method (General) and Conditions
Method 1 Method 2 Method 3
Method
Connecting one indoor unit with 
one solenoid valve kit
Group control is possible by 
connecting plural indoor units to 
one solenoid valve kit.
Indoor units can operate individually 
by connecting plural indoor units to 
one solenoid valve kit. 
Connectable number 
of remote controls
1 piece 1 piece Over 2 pieces
Possible operating 
functions
Individual control
Group control 
*  Thermostat On/Off function 
is possible only in individual 
control (when selecting the body 
thermostat).
Individual control available
*  Mixed group control available
Possible operating 
modes
Cool, Dry, Heating, Auto, Fan Cool, Dry, Heating, Auto, Fan
Cooling, Dry, Heating, Fan
*  Auto selection is impossible.
Condition –
•   Mixed cooling and heating is 
impossible.
•   Mixed cooling and heating is 
impossible.
•   Auto selection is impossible.
Method 1
Indoor unit
Method 1
Indoor unit Indoor unit
Method 2
Indoor unit
Method 3
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Method 3
Solenoid 
valve kit
Remote 
controller
Solenoid 
valve kit
Remote 
controller
Solenoid 
valve kit
Solenoid 
valve kit
Remote 
controller
Indoor unit
Solenoid 
valve kit
Remote 
controller
Remote 
controller
Solenoid 
valve kit
Remote 
controller
Remote 
controller
Remote 
controller
00_341136_2WAY_Eng.indb   34 2022/9/19   9:27:27