27
3-4. Prepare the Tubing
● Material: Use seamless phosphorous deoxidized copper 
tube for refrigeration. Wall thickness shall comply with the 
applicable legislation. The minimal wall thickness must be 
in accordance with the table below. For tubes of ø22.22 or 
larger, use the material of temper 1/2H or H (Hard copper 
tube). Do not bend the hard copper tube.
●  Tubing size 
Use the tubing size indicated in the table below.
●  When cutting the tubing, use a tube cutter, and be sure to 
remove any burrs. 
The same applies to distribution tubing (optional).
●  When bending the tubes, bend each tube using a radius 
that is at least 4 times the outer diameter of the tube. When 
bending, use sufficient care to avoid crushing or damaging 
the tube.
●  For flaring, use a flare tool, and be sure that flaring is 
performed correctly.
CAUTION
Use sufficient caution during preparation of the tubing. 
Seal the tube ends by means of caps or taping to prevent 
dust, moisture, or other foreign substances from entering 
the tubes.
Refrigerant tubing
Tubing size (mm)
Material Temper - O
 (Soft copper tube)
Material Temper - 1/2 H, H 
(Hard copper tube)
Outer dia. Thickness Outer dia. Thickness
ø6.35  t0.8  ø22.22  t1.0
ø9.52 t0.8  ø25.4  t1.0
ø12.7  t0.8  ø28.58  t1.0
ø15.88  t1.0 ø31.75 t1.1
ø19.05 t1.2 ø38.1 over t1.35
ø41.28 over t1.45
3-5. Connect the Tubing
●  When operating the refrigerant tube installation in the 
field, do not apply the flame of welding to the surrounding 
sheet-metal parts. If necessary, use a wet rag to prevent 
overheating of the heat exchanger.
● Use the supplied connector tubing.
1
2
3
4
10/12 HP
Supplied
tube
1
2
3
4
14 HP
16 HP
Supplied
tube
1
2
3
4
Supplied tube
1
2
3
4
Refrigerant  
tubing
Connection 
method
Use 
Supplied 
connector 
tube?
1
Suction tube Brazing No
2
Discharge tube Flare  No
3
Liquid tube Flare  No
4
Balance tube Flare No
Refrigerant  
tubing
Connection 
method
Use 
Supplied 
connector 
tube?
1
Suction tube Brazing No
2
Discharge 
tube
Service valve 
mounted on the 
unit side: Flare 
connection 
Tubing side: 
Brazing
Yes
ø15.88
Flare
↓
ø19.05
Brazing
3
Liquid tube Flare  No
4
Balance 
tube
Flare No
Refrigerant  
tubing
Connection 
method
Use 
Supplied 
connector 
tube?
1
Suction tube Brazing No
2
Discharge 
tube
Brazing
Yes 
ø19.05 
→ø22.22
3
Liquid tube Flare  No
4
Balance 
tube
Flare No
Refrigerant  
tubing
Connection 
method
Use 
Supplied 
connector 
tube?
1
Suction tube Brazing
Yes 
ø25.4 
→ø28.58
2
Discharge 
tube
Brazing
Yes 
ø19.05 
→ø22.22
3
Liquid tube Flare  No
4
Balance 
tube
Flare No
8 HP
Unit: mm
Unit: mm
Unit: mm
10/12 HP
Supplied
tube
1
2
3
4
14 HP
16 HP
Supplied
tube
 
In case of 10/12 HP
Flaring process to the tip of the 
supplied tubes
Use the wide area of the outer tubing 
surface of the supplied tubes.
 
•
 Supplied tubing outer diameter ø19.05
•
 Local tubing inner diameter ø19.05
Remove flare nuts attached to the service 
valve and reuse them.
 
Note: Make sure the service valve is 
completely closed.
 
If not, the gas leak will be occurred.
00_341136_2WAY_Eng.indb   27 2022/9/19   9:27:25