   HOW TO INSTALL THE INDOOR UNIT
 4-Way Cassette Type (Type U1)
Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to check 
that the unit is level.
Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using the 
method shown in the diagrams (Figs. 1-7 and 1-8), by 
attaching them to the ceiling support structure, or by any 
other method that ensures that the unit will be securely 
and safely suspended.
(2) Follow Fig. 1-8 and Table 1-4 to make the holes in the 
ceiling.
Table 1-4  Unit: mm
Length
Type
AB C D
36, 45, 50, 60, 
71, 100, 125, 140
786 745 860 to 910 860 to 910
(3) Determine the pitch of the suspension bolts using the 
supplied full-scale installation diagram. The diagram 
and table (Fig. 1-9 and Table 1-5) show the relationship 
between the positions of the suspension fitting, unit, and 
panel. 
Use the nut (field supply) and washer (supplied) for 
upper and lower position of the suspension lug.
Table 1-5  Unit: mm
Length
Type
ABCDE
36, 45, 50, 60, 71 121 171 256 180 130
100, 125, 140 121 171 319 180 130
Hole-in-anchor
Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8")
(field supply)
Note: For DC Fan Tap Change Procedure for 4-Way 
Cassette, see page 1-351.
Fig. 1-7
Fig. 1-8
Fig. 1-9
Indoor Unit
View from top 
B (suspension bolt pitch)
A (suspension bolt pitch)
C (ceiling opening dimension)
D (ceiling opening dimension)
D
E
A
B
C
33.5
Drain outlet (other side)
(VP25)
Suspension lug
Refrigerant tubing joint (liquid side)
Refrigerant tubing joint (gas side)
Unit: mm