5-235-22
5. Outdoor unit maintenance remote control
List of Item Codes
retemaraPedocmetI
01 Control system schedule
02 Control system schedule
03 Control system schedule
04 Snowfall sensor operation0 = No sensor, control performed
1 = No sensor, control not performed
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
2 = Sensor present, control performed
3 = Sensor present, control not performed
05 Outdoor fan quiet mode Do not set
06 Defrost fan speed selectionDo not set
07 Ignore capacity 0 = Disabled 1 = Ignores capacity ratio
08 Control system schedule
09 Control system schedule
0A Control system schedule
0b Control system schedule
0C Forced operation of 0 = Disabled
indoor unit drain pump1 = During cooling only, 2 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
2 = During cooling only, 4 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
3 = At all times, 4 hours stopped + 20 minutes operating
4 = At all times, 2 hours stopped + 20 minutes operating
0d Odor countermeasure when Do not set
indoor cooling thermostat is OFF
ylnolooC=1pmuptaeH=0ylnolooCE0
0F Control system schedule
10 Control system schedule
11 Multi-floor installation
12
External Electronic Expansion Valve Kit
13 Control system schedule
4E Test mode 1
4F Test mode 2
%061...%001...%54,%041dnameD05
%061...%001...%54,%042dnameD15
52 Current control level 40%, 45% ... 100% ... 160%, –1 (normal: at shipment from factory)
53
Control system schedule55
Do not setControl system schedule54
75
85
95
A5
B5
65
* Figures in parentheses indicate the data at the time of shipment from the factory.
0 = No 1 = Yes
Control system schedule
Control system schedule
Do not setControl system schedule
Do not setControl system schedule
Do not setControl system schedule
Do not setControl system schedule
Do not setControl system schedule
5
SM830203-04.indb 22 15/10/08 13:33:43