15. CHECK OF DENSITY LIMIT
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for installation space of
appliance are determined according to the refrigerant charge amount [m
c
] used in the appliance.
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows:
1.22 3.50 3.88
2.01.51.00.50.0 3.0 4.02.5 3.5 5.04.5
2.5
5.0
7.5
10.0
12.5
15.0
17.5
20.0
22.5
25.0
32.5
35.0
27.5
30.0
0.0
[Amin] : minimum indoor floor space (
m
2
)
[m
c
] : the refrigerant
charge amount (
kg
)
Can not be installed
Can be installed
* U-100PZ2R5, U-100PZ2R8,
U-100PZ2E5, U-100PZ2E8
Can not be installed
[m
c
] : The refrigerant charge amount (Total of refrigerant at shipment and refrigerant charge amount in the field).
[m
max
] : Maximum refrigerant charge amount
U-100PZ2R5
U-100PZ2R8
U-100PZ2E5
U-100PZ2E8
U-125PZ2E5
U-125PZ2E8
U-140PZ2E5
U-140PZ2E8
[m
max
] 3.50 3.50 3.88 3.88
[m
c
] ≤ 1.22 : Can be installed
1.22 < [m
c
] ≤ [m
max
] : Installation possible with in the range of slanted line part
[m
c
] > [m
max
] : Can not be installed