1-23
1
Single-Type
1-1. Unit Specifi cations
PE1
1. 4-Way Cassette Type S-71PU1E5 / U-71PE1E8
INDOOR MODEL S-71PU1E5
PANEL MODEL CZ-KPU2 -
OUTDOOR MODEL U-71PE1E8
Branch pipe MODEL -
PERFORMANCE TEST CONDITION ISO5151 / EN14825
POWER SUPPLY
ø, Hz 1ø 50Hz 3ø 50Hz
V 220 230 240 380 400 415 Min Max
C
O
O
L
I
N
G
CAPACITY
kW 7.1 7.1 7.1 3.2 8.0
BTU/h 24200 24200 24200 10900 27300
CURRENT A 0.36 0.33 0.32 2.80 2.70 2.60 - -
INPUT POWER
W 40 40 40 1.760k 1.760k 1.760k - -
TOTAL W - 1.800k 1.800k 1.800k 560 2.650k
ANNUAL CONSUMPTION
TOTAL W 4 - - 900 - - -
EER/EER CLASS
TOTAL(W/W) 5/("A"~"G")
- - - 3.94 3.94 / A 3.94 5.71 3.02
Erp
6
Pdsign kW - - - - 7.1 -
SEER (W/W) - - - - 6.8 -
Annual consumption
kWh - - - - 365 -
Class - - - - A++ -
POWER FACTOR % - - - 96 94 94 - -
NOISE INDOOR
(H/M/L)
dB-A 37/31/28
Power Level dB 54/48/45
NOISE OUTDOOR
(H/L)
dB-A 48
Power Level dB 65
H
E
A
T
I
N
G
CAPACITY
kW 8.0 8.0 8.0 2.8 9.0
BTU/h 27300 27300 27300 9600 30700
CURRENT A 0.35 0.32 0.31 3.10 3.00 2.90 - -
INPUT POWER
W 40 40 40 1.960k 1.960k 1.960k - -
TOTAL W - 2.000k 2.000k 2.000k 500 2.900k
COP/COP CLASS
TOTAL(W/W) 5/("A"~"G")
- - - 4.00 4.00 / A 4.00 5.60 3.10
Erp
6
Pdsign kW - - - - 7.1 -
Tbivalen °C - - - - -9 -
SCOP (W/W) - - - - 4.0 -
Annual consumption
kWh - - - - 2485 -
Class - - - - A+ -
POWER FACTOR % - - - 96 94 94 - -
NOISE INDOOR
(H/M/L)
dB-A 37/31/28 - ⁄⁄
Power Level dB 54/48/45 -
NOISE OUTDOOR
(H/L)
dB-A - 50 ⁄⁄
Power Level dB - 67
EXTRA LOW TEMP
Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W) 0.36/40 0.33/40 0.32/40 7.0/4.150k 7.0/4.360k 7.0/4.530k ⁄
STARTING CURRENT(A)/COMP OUTPUT(W) - - - 3.10/2.0k 3.00/2.0k 2.90/2.0k ⁄
NETWORK IMPEDANCE (ΩMAX.) - -
FM OUTPUT (W) 60 90 ⁄
MOISTURE REMOVAL VOLUME L/h(Pt/h) 4.2 (8.8) -
External static pressure
Pa
-
I/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 22 (777)
HEAT m
3
/min (ft
3
/min) 22 (777)
O/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 60 (2119)
HEAT m
3
/min (ft
3
/min) 60 (2119)
REFRIGERANT TYPE, AMOUNT
g
(oz) R410A 2.35k (82.9) /
P
R
O
D
I
M
HEIGHT : H mm(inch) 256 (10-3/32) 996 (39-7/32) /
WIDTH : W mm(inch) 840 (33-3/32) 940 (37-1/32) /
DEPTH : D mm(inch) 840 (33-3/32) 340 (13-13/32) /
P
A
C
D
I
M
HEIGHT : H mm 298 1136 /
WIDTH : W mm 929 1055 /
DEPTH : D mm 929 485 /
MASS
(NET) k
g
(lb) 24 (53) 71 (157) /
(GROSS) k
g
(lb) 30 (67) 79 (175) /
LAYERS LIMIT (actually) 11 (12) 2 (3)
Operation
Condition
Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C
Heat (DBT) 16°C ~ 30°C -20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0(16.4) fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 50 (16.4 ~ 164.0) ~ ~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher) (49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50 (537.6)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30 (98.4)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.