(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting.
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Central Controller
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit Indoor unit Indoor unit
Indoor unit Indoor unit
Indoor unit Indoor unit
Outdoor unit
: Branch point
More than 2m required
Outdoor unit Indoor unitIndoor unit
Indoor unitIndoor unit
NO
Branch point
(5) Use shielded wires for inter-unit control wiring (C)
and ground the shield on both sides, otherwise
misoperation from noise may occur.
Connect wiring as shown in Section “4-3. Wiring System
Diagrams”.
SG
SG
Shielded wire
s
Connecting cable between indoor unit and outdoor
unit shall be approved polychloroprene sheathed 5 or
3 *1.5 mm
2
flexible cord. Type designation 60245 IEC57
(H05RN-F, GP85PCP etc.) or heavier cord.
s5SETHESTANDARDPOWERSUPPLYCABLESFOR%UROPE
(such as H05RN-F or H07RN-F which conform to
CENELEC (HAR) rating specifications) or use the
cables based on IEC standard. (60245 IEC57,
60245 IEC66)
WARNING
Loose wiring may cause the terminal to overheat or result
in unit malfunction. A fire hazard may also occur. Therefore,
ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the
instructions on “How to connect wiring to the terminal” and
fasten the wire securely with the terminal screw.