1
1-397
(4) Wall and ceiling side opening position
90
145
135
125
155
90
*
Figure shows view from front.
Figure shows view from top.
ø100 wall side 
opening  (for left-
side drain hose)
ø100 wall 
side opening
ø100 ceiling 
opening
Wall
ø100 ceiling 
opening
Ceiling
Unit: mm
*  If the optional drain up kit is installed, create a ø100 hole 
along the dotted line (part marked with * in fi gure).
Fig. 3-4 
Suspending the Indoor Unit
(1)  Place the full-scale diagram (supplied) on the ceiling at the 
location where you want to install the indoor unit. Use a 
pencil to mark the drill holes (Fig. 3-5).
Wall
Full-scale installation 
diagram
Ceiling
Fig. 3-5 
NOTE
Since the diagram is made of paper, it may shrink or stretch 
slightly because of high temperature or humidity. For this 
reason, before drilling the holes maintain the correct dimensions 
between the markings.
(2)  Drill holes at the 4 points indicated on the full-scale 
diagram.
(3)  Depending on the ceiling type:
 a)  Insert suspension bolts (Fig. 3-6).
or
 b)  Use existing ceiling supports or construct a suitable 
support (Fig. 3-7).
Hole-in-anchor
Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-6
A
A
Ceiling support
Ceiling tiles
Fig. 3-7
WARNING
It is important that you use extreme care in supporting 
the indoor unit from the ceiling. Ensure that the ceiling is 
strong enough to support the weight of the unit. Before 
hanging the ceiling unit, test the strength of each attached 
suspension bolt.
(4)  Screw in the suspension bolts, allowing them to protrude 
from the ceiling (Figs. 3-6 and 3-7). The distance of each 
exposed bolt must be of equal length within 50 mm. 
(Fig. 3-8)
Fixture
Within
50 mm
Ceiling
surface
Unit
Fig. 3-8
(5)  Before suspending the indoor unit, remove the 2 or 3 
screws on the latch of the air-intake grilles, open the 
grilles, and remove them by pushing the claws of the 
hinges (Fig. 3-9). Then remove both side panels sliding 
them along the unit toward the front after removing the 2 
attachment screws. (Fig. 3-10)
Pull out the air-intake grille 
pushing claws of the hinges
Latch
Hinge
Screw
Air-intake grille
Slide
Fig. 3-9
Slide toward 
front side
Side panel
Fig. 3-10
(6)  Carry out the preparation for suspending the indoor unit. 
The suspension method varies depending on whether 
there is a suspended ceiling or not. (Figs. 3-11and 3-12)
(7)  Suspend the indoor unit as follows:
 a)  Mount 1 washer and 2 hexagonal nuts on each 
suspension bolt (Fig. 3-13).
Suspension bolt 
(field supply)
Ceiling surface
Unit
Washer (supplied)
Double nut
(field supply)
Fixture
Fig. 3-11
SM830211-07PAC-i.indb397SM830211-07PAC-i.indb397 2013/09/1722:48:272013/09/1722:48:27