Panasonic U-100PZ2R5 - Type of Copper Tube and Insulation Material

Panasonic U-100PZ2R5
259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
1-11-91
Accessories Supplied with Unit
The accessory parts are supplied inside the indoor unit.
Open the air-intake grille of the indoor unit and take out a
package of accessories.
See the section “Preparation Before Installation”
on page 1-11-85.
Table 1-11-4 (
Ceiling
)
Part Name Figure Q’ty Remarks
Special
washer
4
For temporarily
suspending indoor unit
from ceiling
Drain insulator
2 For drain hose joint
Flare insulator
1 For gas tube joint
1 For liquid tube joints
Clamper
6
For flare insulator and
wiring
Full-scale
installation
diagram
1
For positioning
installation
Drain hose
1
For main unit + PVC pipe
joints
Insulating
tape
2
For gas and liquid tubes
flare nuts
Hose band
1
For drain hose
connection
Side cover (R)
1
(Packed in carton box)
For right side
Side cover (L)
1
(Packed in carton box)
For left side
Screw
2 For side cover (L/R)
Operating
Instructions
1
Installation
Instructions
1
Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local
source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring.
Wire size varies with the total length of wiring.
See the section “1-10. Electrical Wiring” for details.
CAUTION
Check local electrical codes and regulations before
obtaining wire.
Also, check any specified instructions or limitations.
Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your
local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
SM830266-00_大洋州向けR32シングルTD&SM.indb 91 18/03/29 10:21:08