EasyManua.ls Logo

Panasonic U-100PZ2R5 - Operating Range

Panasonic U-100PZ2R5
259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
1-4-1
11
1-4. Operating Range
Cooling
Heating
Temperature
Maximum
Minimum
Maximum
Minimum
Indoor air intake temp.
32°C DB / 25°C WB
18°C DB / 14°C WB
30°C DB / − WB
16°C DB / − WB
Outdoor air intake temp.
43°C DB
-10°C DB
24°C DB/18°C WB
-15°C DB / -15°C WB
10
–10
–5
0
5
10
15
20
25
30
35
40
45
50
Indoor air intake temp. °C (WB)
Outdoor air intake temp. °C (DB)
15
14
16
43
18
20
25
30
Operating
range
10
–15
–20
–25
–10
–5
0
5
10
15
20
25
Indoor air intake temp. °C (DB)
Outdoor air intake temp. °C (WB)
3515 302520
Operating
range
HeatingCooling
SM830266-00_大洋州向けR32シングルTD&SM.indb 1 18/03/29 10:19:40