EasyManua.ls Logo

Panasonic U-10ME2E8 - Page 148

Panasonic U-10ME2E8
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2WAY SYSTEM
Remote Controller Functions
5 - 22
3. Remote Controller Servicing Functions
5
<CZ-RTC4>
List of Servicing Functions
Functions Description Button operation Reset operation Unit status
Test run
Operation with forced
thermostat ON
Press the
button.
Current operation
is maintained.
Sensor
temperature
display
Temperature display
from each sensor
Servicing
check display
Alarm history display
Simple
settings
Filter lifetime, operating
mode priority, central
control address, and
other settings
When settings
are made from a
remote controller,
the indoor unit
where that remote
controller is
connected stops.
Detailed
settings
System address, indoor
unit address, central
control address, and
other settings
Auto address
Auto address setting
based on command
from the wired remote
controller
Automatic reset
Entire system
stops.
Address
change
Change of indoor unit
address
Press the
button.
Press and hold the button for
4 seconds or longer.
Press and hold the and
buttons for 4 seconds or longer.
Press and hold the and
buttons for 4 seconds or longer.
Press and hold the , and
buttons for 4 seconds or
longer.
Press and hold the and
buttons for 4 seconds or longer.
Press and hold the and the
timer operation buttons for 4
seconds or longer.
Press and hold the and the
timer operation buttons for 4
seconds or longer.
2WAY SYSTEM
Remote Controller Functions
3. Remote Controller Servicing Functions
Test Run Function
Operates the unit with the thermostat forced ON.
<Procedure of CZ-RTC5A>
1
Keep pressing the , and
buttons simultaneously for 4 or more seconds.
The “Maintenance funcscreen appears on the
LCD display.
2
Press the or button to see each
menu.
If you wish to see the next screen instantly, press
the
or button.
Select "4. Test run" on the LCD display and press
the
button.
Change the display from OFF to ON by pressing
the or button. Then press the
button.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel. Page [] Confirm
Sel. Page [] Confirm
20:30 (THU)
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
20:30 (THU)
[] Confirm
Test run
Change
20:30 (THU)
Test run
ON
3
Press the button. “TESTwill be displayed
on the LCD display.
4
Press the button. Test run will be started.
Test run setting mode screen appears on the LCD
display.
TEST
START[]
20:30 (THU)
TEST
20:30 (THU)
COOL
MODE
FAN SPEED
FLAP
START
[]
20:30 (THU)
SM830253-00_欧州2way7_SM-TRSM.indb 22 16/08/02 14:00:33

Table of Contents

Related product manuals