2WAY SYSTEM
Control Functions - Outdoor unit
1
13. Detailed Settings in EEPROM of Outdoor
Unit
Never use the DN code unlisted in the following table. (P) : at factory shipment
DN Item Setting No.
04 Operation for using snowfall sensor
0=No sensor & control (P) 1=Sensor & control
2=No sensor & no control 3=Sensor & no control
(For details, see "5. Outdoor Unit Fan Control (8)")
05 Outdoor fan silent mode
0=Invalid (P) 1=Silent mode 1
2=Silent priority & silent mode 2,,,,, 12=Silent mode 12
(For details, see "5. Outdoor Unit Fan Control (6)")
0C Indoor unit drain pump forced operation
0=Invalid
1=stop for 2 hours and drive for 20 minutes constantly
2=stop for 20 minutes and drive for 20 minutes constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
(For details, see "6. Outdoor Unit CCU Control (4)")
0D
Measures against smell when indoor unit cooling
thermostat OFF
0=Invalid (P)
1=Measures against smell
19
Setting of control validity range when pressing the
Energy saving button
0=for group (P)
1=for refrigerant system
(For details, see “10. Demand control (2)”)
1A Demand 1 current (%)
0=0% 40=40%
45=45%,,,,, 100=100% (P) ,,,,,
130=130% -1=No control
(For details, see "10. Demand Control")
1B Demand 2 current (%)
0=0% 40=40%
45=45% 70=70% (P) ,,,,,
130=130% -1=No control
(For details, see "10. Demand Control")
1E Demand remote controller display
0=No demand display
1=When demand ON, “demand - actived” display (P)
2=When forced thermostat OFF with demand ON,
“demand - actived” display
(For details, see "10. Demand Control")
23 E06 ignore function
-1=Invalid (P) 0=0
1=1 ,,,,, 16=16
17 - 64=Never use
(For details, see "12. Other Functions")
24 Indoor Unit Self Oil Recovery Control
0=fan stop
1=fan operate & Te +5°C shift
(For details, see “7. Oil control (6)”)
27
Auto Cooling / Heating Functions mode change mask
time
0=Invalid (P) 30=30 minutes
40=40 minutes ,,,,, 240=240 minutes
(For details, see "12. Other Functions (1)")
2A Dew condensation prevention control of indoor unit
0=Invalid (P) 1=30 minutes
2=40 minutes 3=50 minutes
4=60 minutes
2B DP operation time for slime measures
20=20 minutes 30=30 minutes (P)
40=40 minutes 50=50 minutes
60=60 minutes
(For details, see "6. Outdoor Unit CCU Control (4)")
3E Delay-start for each system
0=No delay-start for each system
1=(system address x1x8) seconds delay
2=(system address x2x8) seconds delay
3=(system address x3x8) seconds delay
(For details, see "2. Selecting Outdoor Unit for Operation (2)")
4C
Setting of remote controller inspection display in
automatic backup mode
0=Display (P) 1=non-displayed
3WAY SYSTEM
Control Functions
13. Other Functions
(2) Maintenance Function for Power Supply Stop of Indoor Unit (E06 ignore)
The system can continue operation even if outdoor unit cannot communicate with some indoor units.
It is necessary to set to EEPROM the allowed number of operating indoor units not to be able to communicate.
The system will continue operating until the following condition is made to be satisfied.
Value set by the code “23” ≥No. of indoor units operated until the last moment because of communicative
disorder caused by power supply stop (excluding stopped indoor units).
However, the upper limit value set by the code "23" must be less than 25% of the total number of indoor units
of the system.
EEPROM setting in main outdoor unit
CODE: 23
Allowed number of missing indoor unitSetting No.
-1
This function is invalid
(at factory shipment)
Interval of “1”
0 0
1 1
22
1616
Never use
17
64
Examples :
In case of 8 indoor units, setting No. becomes “2”.
* However, the upper limit value set by the code "23" must be less than 25% of the total number of indoor
units of the system.
SM830228-023WAYECO-iSYSTEM.indb48 2014/02/1918:01:20
ON ON ON ON ON OFF OFF OFF
ON ON ON ON ON OFF OFF OFF
ON ON ON ON ON OFF OFF OFF
Operation continue: Stopped units does not count
Normal operation
Error occurs: Indoor unit failure=3 > Setting No “2”
Operation continue: Indoor unit failure=2 Setting No “2