2WAY SYSTEM
Remote Controller Functions
5 - 27
3. Remote Controller Servicing Functions
5
<Procedure of CZ-RTC4>
1
Press and hold the and buttons
simultaneously for 4 seconds or longer.
2
The unit No. “X-X” (main unit No.), item code “
”
(sensor address), and servicing monitor “ ”
(sensor temperature) are displayed on the remote
controller LCD display.
3
Press the temperature setting /
and select the item code to the address of the
buttons
sensor to monitor.
4
If group control is in effect, press the
to select the unit to monitor.
button
Press the temperature setting buttons to select the
item code to change.
5
Press the button to return to normal remote
controller display.
NOTE
The temperature display appears as “- - - -” for unit that are not connected.
* If monitor mode is engaged while normal operation is in progress, only the parts of the LCD display shown in the
figure will change. Other parts continue to display the same information as during normal operation.
* Display shows a discharge temperature of
00XX at unit No. 1-1.
A
°
°
3
3
4
1
2
4 5
4
Indoor unit sensors
00 Room temp. controlled*
01 Remote controller temp.
02 Indoor unit intake temp. (TA)
03
Indoor unit heat exchanger
temp. E1 (E1)
04 —
05
Indoor unit heat exchanger
temp. E3 (E3)
06 Discharge air temp. (BL)
07 Discharge air temp. setting
08 Indoor unit MOV pulse (MOV)
Outdoor unit sensors
Unit No.1 Unit No.2 Unit No.3 Unit No.4
0A 2A 4A 6A Discharge temp. 1 (DISCH1)
0B 2B 4B 6B Discharge temp. 2 (DISCH2)
0C 2C 4C 6C High-pressure sensor temp.
0D 2D 4D 6D Heat exchanger gas 1 (EXG1)
0E 2E 4E 6E Heat exchanger liquid 1 (EXL1)
0F 2F 4F 6F Heat exchanger gas 2 (EXG2)
10 30 50 70 Heat exchanger liquid 2 (EXL2)
11 31 51 71 Outdoor air temp. (TO)
12 32 52 72 Inverter1 secondary current
13 33 53 73 Inverter1 primary current (L2 phase)
14 34 54 74 Inverter2 primary current (L2 phase)
15 35 55 75 MOV pulse 1 (MOV1)
16 36 56 76 MOV pulse 2 (MOV2)
18 38 58 78 Inverter2 secondary current
19 39 59 79 Inverter1 actual operating frequency
1A 3A 5A 7A MOV pulse 4 (MOV4)
1B 3B 5B 7B Inverter1 primary current (L1 phase)
1C 3C 5C 7C Inverter2 primary current (L1 phase)
1D 3D 5D 7D Low-pressure sensor temp.
1E 3E 5E 7E Suction temp. (SCT)
1F 3F 5F 7F Detected oil temp. 1 (OIL1)
20 40 60 80 Detected oil temp. 2 (OIL2)
21 41 61 81 Inverter1 primary current (L3 phase)
22 42 62 82 Inverter2 actual operating frequency
24 44 64 84
Temp. sensor at refrigerant gas outlet of
dual-tube temp. (SCG)
25 45 65 85 Inverter2 primary current (L3 phase)
*Room temp. controlled: = Controlled room temperature
•Whenbodythermostatcontrolled:
Controlled room temperature = Indoor unit intake temp. (TA) – Intake temperature shift (*1)
•Remotecontrolthermostatcontrolled:
Controlled room temperature = Remote controller temp.
*1 Intake temperature shift: This is the shift value considered the temperature difference between the upper area
and lower area of the room in heating mode.
It is the value of the code “06” in the indoor unit’s EEPROM setting.
Cooling mode: = 0