3WAY SYSTEM
Remote Controller Functions
4 - 10
2. Detailed Settings Function
4
Simple setting items
Item code Item Description
01
Filter sign ON time setting
(filter lifetime)
Changes the indoor unit filter lifetime when a high-performance filter or other
optional product is installed.
02 Degree of filter fouling
Reduces the filter sign ON time to 1/2 of the standard time (setting at the time of
shipping) for cases when filter fouling is more severe than normal.
Filter sign ON times for each model
Model
data
Model
Filter sign ON time
Standard Long-life
Super
long-life
High
performance
65
High
performance
90
Pressure
differential
switch
0001 4-Way cassette (U1, Y1) × × 2500 1250 5000 2500 2500 1250 ×× ×
0002 2-Way cassette (L1) × ×
2500 1250
10000
5000 2500 1250 2500 1250 ×
0003 1-Way cassette (D1) × ×
2500 1250 ×××××× ×
0005
Low Silhouette Ducted (F1,F2)
Slim Low Static Ducted (M1)
×××1250 5000 2500
2500 1250 5000 2500 ×
0006
High Static Pressure Ducted (E1)
×××1250 ××2500 1250 5000 2500 ×
0007 Ceiling (T1) × ×
2500 1250 ××2500 1250 ×× ×
0008 Wall Mounted (K1)
150 75 ×××××××× ×
0010 Floor Standing (P1)
150 75 ×××××××× ×
0011 Concealed Floor Standing (R1)
150 75 ×××××××× ×
Unit: hour
NOTE
×
indicates that there is no corresponding filter.
150
indicates the filter sign ON time that is set at shipment.
High fouling: Set when
is selected for the degree of filter fouling (item code ).
•
•
•
Standard
Standard
Standard
Standard
Standard
High
fouling
High
fouling
High
fouling
High
fouling
High
fouling