3WAY SYSTEM
Control Functions
1 - 50
1
14. Detail setting in EEPROM of outdoor unit
DN Item Setting No.
04 Operation for using snowfall sensor
0=No sensor & control (P) 1=Sensor & control
2=No sensor & no control
(For detail, refer to 5-1-3)
(For detail, refer to 5-1-4)
3=Sensor & no control
05 Outdoor fan silent mode
0=Invalid (P)
2=Silent priority & silent mode 2,,,,, 12=Silent mode 12
1=Silent mode 1
(For detail, refer to 6-4)
0C Indoor unit drain pump forced operation
0=Invalid
1=stop for 2 hours and drive for 20 min. constantly
2=stop for 20 min. and drive for 20 min. constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
8-11=delay drive when stopped
12-15=Delay drive when thermostat OFF & stopped
1A
Demand 1 current ()
0=0% 40=40%
45=45%,,,,, 100=100% (P) ,,,,,
140=140% -1=No control
(For detail, refer to 10-1)
1B
Demand 2 current ()
0=0% 40=40%
45=45% ,,,,, 70=70% (P) ,,,,,
140=140% -1=No control
(For detail, refer to 10-1)
0D
Measures against smell when indoor unit cooling
thermostat OFF
0=Invalid (P)
1=Measures against smell
(For detail, refer to 13-1)
(For detail, refer to 10-1)
23 E06 ignore function
1E Demand remote controller display
0=No demand display
1=When demand ON, “ready to start” display (P)
2=When forced thermostat OFF with demand ON,
“ready to start” display
Never use the DN code unlisted in the following table. (P) : Factory preset mode
2A Dew condensation prevention control of indoor unit
0=Invalid (P) 1=30 min.
2=40 min. 3=50 min.
4=60min.
2B DP operation time for slime measures
20=20 min 30=30 min. (P)
40=40 min.
50=50 min.
60=60 min.
(For detail, refer to 6-4)
3E PSccutgt delay-start setting
0=8 second delay-start (P)
1=(system address x1x8) second delay-start
2=(system address x2x8)
3=(system address x3x8)
1=non-displayed
49 Automatic backup mode setting
0=Display (P)
(For detail, refer to 12-1-4)
81 Outdoor unit capacity
0=Invalid
2=25 3=281=22
6=40
4=32
7=455=36
10=63
8=50
11=719=56
14=100 15=11213=90
12=80
18=160
16=125
19=18017=140
22=250 23=28021=22420=200
26=40024=335 27=45025=355
30=600 31=63029=56028=500
34=800 35=84033=71032=670
8F High static pressure setting
0=Invalid (P) 1=High static pressure mode
2=Never use
(For detail, refer to 5-1-2)
3=Never use
4=Never use
5=Never use
6=Never use
13=131=1 ,,,,,
14 - 52=Never use
0=0-1=Invalid (P)
SM830226-003WAYECO-iSYSTEM.in5050SM830226-003WAYECO-iSYSTEM.in5050 2013/02/1311:52:302013/02/1311:52:30