4
For WH-SDC0309K3E5, WH-SDC0309K6E5
Table I – Maximum refrigerant charge allowed in a room
A
room
(m
2
)
Maximum refrigerant charge in a room
(
m
max
) (kg)
H
=
1.15m
H
=
1.20m
H
=
1.30m
H
=
1.40m
H
=
1.50m
H
=
1.60m
H
=
1.70m
H
=
1.80m
1 0.265 0.276 0.299 0.322 0.345 0.368 0.391 0.414
2 0.530 0.553 0.599 0.645 0.691 0.737 0.783 0.829
3 0.794 0.829 0.898 0.967 1.036 1.105 1.174 1.243
4 1.059 1.105 1.197 1.289 1.382 1.474 1.566 1.658
5 1.324 1.382 1.497 1.612 1.727 1.842 1.957 2.072
6 1.589 1.658 1.796 1.934 2.072 2.210 2.349 2.487
7 1.738 1.814 1.965 2.116 2.267 2.418 2.570 2.721
8 1.858 1.939 2.101 2.262 2.424 2.585 2.747 2.909
9 1.971 2.057 2.228 2.399 2.571 2.742 2.914 3.085
10 2.078 2.168 2.349 2.529 2.710 2.891 3.071 3.252
11 2.179 2.274 2.463 2.653 2.842 3.032 3.221 3.411
12 2.276 2.375 2.573 2.771 2.969 3.166 3.364 3.562
13 2.369 2.472 2.678 2.884 3.090 3.296 3.502 3.708
For intermediate
H
values, the value that corresponds to the lower
H
value from the table considered.
Example:
For
H
=
1.25 m, the value that corresponds to “
H
=
1.20 m” is
considered.
For intermediate
A
room
values, the value that corresponds to the
lower
A
room
value from the table is considered.
Example:
For
A
room
= 10.5 m
2
, the value that corresponds to
A
room
= 10 m
2
” is considered.
Table II – Minimum floor area
m
c
(kg)
Minimum floor area
(
A
min total
(m
2
))
H
=
1.15m
H
=
1.20m
H
=
1.30m
H
=
1.40m
H
=
1.50m
H
=
1.60m
H
=
1.70m
H
=
1.80m
1.84 7.84 7.20 6.15 5.71 5.33 4.99 4.70 4.44
1.86 8.02 7.36 6.27 5.77 5.39 5.05 4.75 4.49
1.88 8.19 7.52 6.41 5.83 5.44 5.10 4.80 4.54
1.90 8.36 7.68 6.54 5.89 5.50 5.16 4.85 4.58
1.92 8.54 7.84 6.68 5.96 5.56 5.21 4.91 4.63
1.94 8.72 8.01 6.82 6.02 5.62 5.27 4.96 4.68
1.96 8.90 8.17 6.96 6.08 5.67 5.32 5.01 4.73
1.98 9.08 8.34 7.11 6.14 5.73 5.37 5.06 4.78
2.00 9.27 8.51 7.25 6.25 5.79 5.43 5.11 4.83
2.02 9.45 8.68 7.40 6.38 5.85 5.48 5.16 4.87
2.04 9.64 8.85 7.54 6.51 5.91 5.54 5.21 4.92
2.06 9.83 9.03 7.69 6.63 5.96 5.59 5.26 4.97
2.08 10.02 9.21 7.84 6.76 6.02 5.65 5.31 5.02
2.10 10.22 9.38 8.00 6.89 6.08 5.70 5.37 5.07
2.12 10.41 9.56 8.15 7.03 6.14 5.75 5.42 5.12
m
c
(kg)
Minimum floor area
(
A
min total
(m
2
))
H
=
1.15m
H
=
1.20m
H
=
1.30m
H
=
1.40m
H
=
1.50m
H
=
1.60m
H
=
1.70m
H
=
1.80m
2.14 10.61 9.74 8.30 7.16 6.24 5.81 5.47 5.16
2.16 10.81 9.93 8.46 7.29 6.35 5.86 5.52 5.21
2.18 11.01 10.11 8.62 7.43 6.47 5.92 5.57 5.26
2.20 11.21 10.30 8.77 7.57 6.59 5.97 5.62 5.31
2.22 11.42 10.49 8.93 7.70 6.71 6.03 5.67 5.36
2.24 11.62 10.68 9.10 7.84 6.83 6.08 5.72 5.40
2.26 11.83 10.87 9.26 7.98 6.96 6.13 5.77 5.45
2.28 12.04 11.06 9.42 8.13 7.08 6.22 5.82 5.50
2.30 12.26 11.26 9.59 8.27 7.20 6.33 5.88 5.55
For intermediate
H
values, the value that corresponds to the lower
H
value from the table considered.
Example:
For
H
=
1.25 m, the value that corresponds to “
H
=
1.20 m” is considered
.
For intermediate
m
c
values, the value that corresponds to the higher
m
c
value from the table is considered.
Example:
If
m
c
= 1.85 kg, the value that corresponds to “
m
c
= 1.86 kg” is
considered.
Systems with total refrigerant charge lower than 1.84 kg are not
subjected to any room area requirements.
Charges above 2.30 kg are not allowed in the unit.
Table III – Minimum venting opening area for natural ventilation
m
c
(kg)
m
max
(kg)
m
excess
(kg)
=
m
c
-
m
max
Minimum venting opening area
(
VA
min
) (cm
2
)
H
=
1.15m
H
=
1.20m
H
=
1.30m
H
=
1.40m
H
=
1.50m
H
=
1.60m
H
=
1.70m
H
=
1.80m
2.3 0.1 2.2
643 629 605 583 563 545 529 514
2.3 0.3 2.0
584 572 550 530 512 495 481 467
2.3 0.5 1.8
526 515 495 477 461 446 433 420
2.3 0.7 1.6
468 458 440 424 409 396 385 374
2.3 0.9 1.4
409 400 385 371 358 347 336 327
2.3 1.1 1.2
351 343 330 318 307 297 288 280
2.3 1.3 1.0
292 286 275 265 256 248 240 234
2.3 1.5 0.8
234 229 220 212 205 198 192 187
2.3 1.7 0.6
179 172 165 159 154 149 144 140
2.3 1.9 0.4
126 121 112 106 102 99 96 93
2.3 2.1 0.2 66 64 59 54 51 50 48 47
2.3 2.2 0.1 34 33 30 28 26 25 24 23
For intermediate
H
values, the value that corresponds to the lower
H
value from the table considered.
Example:
For
H
=
1.25 m, the value that corresponds to “
H
=
1.20 m” is
considered.
For intermediate
m
excess
values, the value that corresponds to the
higher
m
excess
value from the table is considered.
Example:
m
excess
= 1.45 kg, the value that corresponds to “
m
excess
= 1.6 kg
is considered.