10
Safety precautions
2-2.  Work
• Prior to beginning work on systems 
containing fl ammable refrigerants, 
safety checks are necessary to 
ensure that the risk of ignition 
is minimised. For repair to the 
refrigerating system, the precautions 
in #2-2 to #2-8 must be followed 
before conducting work on the 
system.
• Work shall be undertaken under 
a controlled procedure so as to 
minimize the risk of a fl ammable gas 
or vapour being present while the 
work is being performed.
• All maintenance staff and others 
working in the local area shall be 
instructed and supervised on the 
nature of work being carried out.
• Avoid working in confi ned spaces. 
Always ensure away from source, at 
least 2 meter of safety distance, or 
zoning of free space area of at least 
2 meter in radius.
• Wear appropriate protective 
equipment, including respiratory 
protection, as conditions warrant.
• Keep all sources of ignition and hot 
metal surfaces away.
2-3.  Checking for presence of 
refrigerant
• The area shall be checked with an 
appropriate refrigerant detector prior 
to and during work, to ensure the 
technician is aware of potentially 
fl ammable atmospheres.
• Ensure that the leak detection 
equipment being used is suitable for 
use with fl ammable refrigerants, i.e. 
non sparking, adequately sealed or 
intrinsically safe.
• In case of leakage/spillage 
happened, immediately ventilate 
area and stay upwind and away from 
spill/release.
• In case of leakage/spillage 
happened, do notify persons down 
wind of the leaking/spill, isolate 
immediate hazard area and keep 
unauthorized personnel out.
2-4.  Presence of fi re extinguisher
• If any hot work is to be conducted 
on the refrigerating equipment or 
any associated parts, appropriate 
fi re extinguishing equipment shall be 
available at hand.
• Have a dry powder or CO
2
 fi re 
extinguisher adjacent to the charging 
area.