ESPRIT 728 WIRING DIAGRAM
GREEN
1K
EOL
RES
Ω
GREEN
1K
EOL
Ω
KEYPAD
MAX 5 per system*
ZONE 7 or 8
TAMPER
Smoke and heat detectors
BLK
GRN
YEL
RED
( is considered as keypad)PS1
GRN
YEL
RED
BLK
ZONE
COM
N.C.
N.O.
N.C.
N.O.
GREEN
1K
EOL
Ω
P R DOXP R DOX
RMED RE DY
To cabinet and grounding rod
-+
T - 1
R- 1
TIP
RING
BATT
5AMP
DIALER
+AUX -
+BELL -
AC
PGM
+
COM1/4 2/5
3/6
GRN YEL
+
+
+
+
BLACK
RED
BELL
SIREN
-+
TRANSFO
16.5VAC 40VA
N.O. contacts
8 ZONE CONTROLLER/COMMUNICATOR
ESPRIT
728
-
+
BRN
GRY
GRN
RED
SECURITY SYSTEMS
Charging and battery test LED
(every 60 seconds)
SERIAL
OUTPUT
RESET
JUMPER
"TLM" LED
Short flash = OK
Long flash = Fault
OFF = Disabled
Constant
= On Line
RJ31X
CA 38A
BATT
RECHARGEABLE
BATTERY
UL/ULC 12VDC
7AH required.
UL: K12 model T16 V40
ULC: Frost model FTC 1637
Caution: Disconnect battery
before replacing fuse.
A.C.
POWER
BELL OUTPUT
UL/ULC 650mA max.
will shut down
if current
exceeds 3A.
AUX POWER
400mA max.
UL/ULC 250mA max. for
24 hr. standby. Aux Power
will shut down if
current exceeds 1A.
ZONE
7 OR 8
*Zone 3 = Fire zone
If definition is
selected
24 hour zone.
For zone connections
see diagrams below
PS1
ESPRIT arming / panic module
PGM OUTPUT RELAY
BLK RED
YELBRN
COM N.C. N.O.
+AUX
PGM
MR3-UL
For smoke detector reset PGM1
Address
196
198
Data
[5] [3]
[2] [2 ]
ND
WHT
Keyswitch can be used in parallel with keypad (or PS1),
(not on UL systems).
Warning: Improper connection may
result in damage to the system.
Warning:
Disconnect
telephone line
before servicing.
Not on
UL systems
GROUND START CIRCUIT
RNG
WHT
BLK RED
YEL
MR3-UL
+AUX
PGM
Not permitted on UL listed sytems.
UL/ULC: Wheelock 46T-12
TYPICAL (UL/ULC)
ZONE CONNECTIONS
Zone input COM
TAMPER TAMPER
N.C.
N.C.
BROWN
.5KΩ
BROWN
.5KΩ
BROWN
.5KΩ
GREEN
1KΩ
EOL EOL
Advanced Technology Zoning with EOL resistor
To reset smoke detectors, press [TRBL] + [11]
COM
PGM
*
* PGM maximum 50mA
Z3
AUX
+
GREEN
1K
EOL
Ω
+
+
-
-
Smoke detector
power supervision
relay, 12VDC
Smoke detector must be 4 wire latching -
UL Falcon model 5454, ULC BRK 2412
Power supervision relay model MR3-UL.
FIRE ALARM ZONE
CONNECTIONS
Smoke
detector
Smoke
detector
PN2011 00200-PRT
KEYSWITCH
KEYSWITCH CONNECTION
KYPD GRN
KYPD BLK
220Ω
*
*
SECURITY SYSTEMS
780 Industrial Blvd., St-Eustache, Montreal, Quebec, Canada J7R 5V3 Fax: (514) 491-2313 http://www.paradox.ca
Paradox Security Systems Graphic Dept
PRINTED IN CANADA
960603
ESPRIT 728
Calculation of the auxiliary supply current must
include reduction to available current due to total
keypad consumption.
*