Programming steps to the PARADOX MG5050 Control panel
working in conjunction to RDC transmitters.
Connecting the transmitter to the panel:
Connect the R (RING) wire to the transmitter negative. Connect the T (TIP) wire to the transmitter CID
connection. Power the transmitter directly from the battery.
Entering programming:
Press ENTER 0 0 0 0 (This is the default code)
Programming the communicator:
The keypad expects a 3-digit section number
Press 800 Programming of the communicator options
Ensure 1, 2, 5, 6 is on
1 is TLM trouble
2 is TLM reporting
5 is Tone dial
6 is force dial
Press 801 Program reporting options
Ensure 1 is off and 2 is on
1 off - Always report disarming
2 on - Zone restoral reports on zone closure
Press 802 Program reporting options
Ensure 1 and 5 is on
1 on Report Arm/disarm on MSTN 1
5 on Report Alarms/restores on MSTN 1
Press 803 Program reporting options
Ensure 1 is on
1 on Report Tamper/restores on MSTN 1
Press 804 Program reporting options
Ensure 1 is on
1 on Special reporting on MSTN 1
Press 838 Closing delay to be 000 seconds
Press 851 Armed report delay (default is 5min)
Set it to 001 for 1min

Other manuals for Paradox MG5050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Paradox MG5050 and is the answer not in the manual?

Paradox MG5050 Specifications

General IconGeneral
Partitions2
User Codes32
Wireless Zones32
Event Buffer256 events
Remote ControlsSupports up to 32 remote controls
Standby Current85 mA
Zones32
CommunicationGSM
Humidity5% to 90% non-condensing
Input Voltage16.5 VAC

Related product manuals