FIGURE 1 TEST SET-UP
5.0 DIFFERENTIAL PRESSURE TRANSDUCER CALIBRATION PROCEDURE
(Refer to Figure 1 For Test Set-Up)
5.1 Equipment Needed
5.1.1 4-1/2 Digit Multi Meter (Fluke Model 8062A Or Equivalent DMM)
5.1.2 Precision Manometer (Ashcroft Model ATE-100 Or Equivalent)
5.1.3 Compressed Air source (Paragon Model AP-100 Air Pump)
5.1.4 Low Pressure Signal Generator (Paragon Model PS-100)
5.1.5 Potentiometer Adjustment Tool (Spectrol)