7 Ricerca guasti
GUASTO
CAUSA
RIMEDIO
LA TEMPERATURA
DELL’ACQUA IN USCITA
E’ SUPERIORE AL VALORE
IMPOSTATO
IL COMPRESSORE SI
FERMA PER INTERVENTO
DEL PRESSOSTATO DI ALTA
PRESSIONE
ASPIRAZIONE
COMPRESSORE,
LINEA LIQUIDO
BRINATI
IL COMPRES-
SORE
FUNZIONA
LUNGAMENTE,
E’ RUMOROSO
PORTATA ACQUA
ECCESSIVA, CARICO
TERMICO ELEVATO
DIMINUIRE LA PORTATA
DEL FLUIDO DA RAFFRED-
DARE
TEMPERATURA
AMBIENTE
ELEVATA
RIPORTARE LA
TEMPERATURA
AMBIENTE SOTTO IL
VALORE LIMITE
DICHIARATO
PRESSOSTATO
ROTTO O
STARATO
SOSTITUIRE IL
PRESSOSTATO
FILTRO
REFRIGERANTE
INTASATO
SOSTITUIRE
IL FILTRO
ALETTE DEL
CONDENSATORE
SPORCHE
PULIRE LE
ALETTE DEL
CONDENSATORE
SUPERFICIE DEL
CONDENSATORE
OSTRUITA
LIBERARE LA
SUPERFICIE
FRONTALE DEL
CONDENSATORE
PORTATA
ACQUA
INSUFFICIENTE
AUMENTARE
LA PORTATA DEL
FLUIDO DA RAF-
FREDDARE
COMPONENTI
COMPRESSORE
DETERIORATI
RIPARARE O
SOSTITUIRE
COMPRESSORE
PERDITE NEL
CIRCUITO,
IMPIANTO SCARICO
VERIFICARE LA
PRESENZA DI
PERDITE, ELIMINARLE,
CARICARE IL
CIRCUITO
FILTRO
REFRIGERANTE
INTASATO
SOSTITUIRE
IL FILTRO
si
no
si
si si
si si
si
si
si
si
no
no
no
no
IL COMPRESSORE SI
FERMA PER INTERVENTO
DEL PRESSOSTATO DI BASSA
PRESSIONE
no
VENTILATORE
GIRA ROVESCIO
no
INVERTIRE
LE FASI
BULBO
TERMOSTATO
SCARICO
no
VALVOLA
TERMOSTATICA
STARATA
no
SOSTITUIRE
LA VALVOLA
RITARARE
LA VALVOLA
si
si
no
no
si