Do not use means to accelerate the defrosting process or to clean, other than those recommended by the
manufacture.
The appliance shall be stored in a room without continuously operation sources (for example: open flames,
an operating gas appliance or an operating electric heater).
The appliance shall be stored so as to prevent mechanical damage from occurring.
Do not piece or burn, even after use.
Be aware that refrigerants may not contain an odour.
Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if
that space is smaller than 4 m².
Compliance with national gas regulations shall be observed.
Keep any required ventilation openings clear of obstruction.
The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as
specified for operation.
WARNING
Any person who is involved with working on or breaking into a refrigerant circuit should
hold a current valid certificate from an industry-accredited assessment authority, which
authorizes their competence to handle refrigerants safely in accordance with an industry,
recognized assessment specification.
WARNING
Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be carried
out under the supervision of the person competent in the use of flammable refrigerants.
2.2 SAFETY PRECAUTIONS ON SERVICING
Please follow these warnings when to undertake the following when servicing an appliance with R32.
2.2.1 Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk
of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to
conducting work on the system.
2.2.2 Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being