MANUALE D’USO – USER MANUAL
INTERVENTION TO BE PERFORMED
FREQUENCY
Check for water leaks inside the humidifier.
after 1 hour of functioning
Check fastening of electric connections.
after 4 weeks of
functioning
Check for water leaks inside the humidifier.
Check cylinder status; eliminate any scaling and deposits from inside,
if present.
If necessary, replace cylinder.
monthly or every
500 hours of functioning
Check cylinder electrodes consumption and absence of deformations
or blackening on their surface; replace cylinder if worn and having
evident defects.
three-monthly or every
1000 hours of functioning
Replace cylinder.
Check fastening of the electric connections and good status of the
water and steam connections.
yearly or every
2500 hours of functioning
Check for water leaks inside the humidifier.
Check cylinder status; check wear of the electrodes and eliminate any
scaling and deposits from inside, if present and, if necessary, replace
cylinder.
Upon occurring of alarm
code E1
Check for water leaks inside the humidifier.
Verify the water charge valve is not disconnected or faulty, if so
replace it.
Upon occurring of alarm
code E3
Check the discharge pump is not disconnected or faulty and, if so,
replace it.
If present, remove any clogging from bottom of cylinder and inside
discharge tubes.
Upon occurring of alarm
code E5 or E6