H-System – Isolated Barriers and Termination Boards
Dismounting, Maintenance, and Repair
6 Dismounting, Maintenance, and Repair
Disconnecting Circuits
1.
Disconnect the power supply.
2. Disconnect the field circuit.
3. Disconnect the control circuit.
Danger!
Danger to life from using damaged or repaired devices.
Using a defective or repaired device can compromise its function and its electrical safety.
Do not use a damaged or polluted device.
The device must not be repaired, changed or manipulated.
If there is a defect, always replace the device with an original device from Pepperl+Fuchs.
Danger!
Explosion hazard from live wiring of non-intrinsically safe circuits
If you connect or disconnect energized non-intrinsically safe circuits in a potentially explosive
atmosphere, sparks can ignite the surrounding atmosphere.
Only connect or disconnect energized non-intrinsically safe circuits in the absence
of a potentially explosive atmosphere.
Danger!
Explosion hazard from changing the fuse
The changing of the fuse under voltage can cause sparks. This can ignite the surrounding
potentially explosive atmosphere.
De-energize the device before changing the fuse.