2017-12
16
Functional Safety KF**-CRG2-(Ex)1.D
Mounting and Installation
Configuring the Device via PACTware Operating Software
The device can also be configured via the PACTware operating software. The
interface for connecting a personal computer for configuring is on the front of the
device.
1. Open the cover.
2. Connect a personal computer via the K-ADP-USB adapter to the device.
3. Configure the device for the required safety function via the PACTware
operating software, see chapter 4.1.1.
4. Protect the device configuration by a password against changing.
5. Leave the parameterization mode to prevent unintentional adjustments.
6. Disconnect the personal computer from the device.
7. Close the cover.
8. Check the device configuration to ensure the expected output behavior.
9. Document any changes to the device configuration.
4.1.1 Configuration for Use in Safety Function
Configuring the Device for Use in Safety Function
1. Configure the device for the required safety function via the keypad or the
operating software.
2. Enable the short circuit (SC) detection and lead breakage (LB) detection.
3. Disable the HOLD function.
4. Set the characteristic of the current output to the 4 mA to 20 mA NE 43 mode.
5. Set the fault current of the current output to "Min" or "Max".
6. Protect the device configuration by a password against changing.
Note!
For more information see the manual.
Note!
For more information see the manual.