9 Installations
For effective cooling & ventilation, correct installation & ventilation of the cooling unit is very important.
The distance must be kept at least 500mm between units or the unit to the wall.
The requires at least 40mm space and the electrical components shall not
impede air circulation in the internal cabinet.
The power supply must be switched off when installing the cooling unit.
The site of installation must be protected against contamination.
the cooling unit is mounted on an switch cabinet door, it must be confirmed that hinges can support the additional
weight or that the switch cabinet will not topple over when the door is opened.